6 bristol controlwave micro, Wiring plan, Parameter – VEGA VEGAPULS 65 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol User Manual

Page 68

Advertising
background image

68

11 Supplement

VEGAPULS 65 • Modbus and Levelmaster protocol

41365-EN-121011

11.6 Bristol ControlWave Micro

Wiring plan

+

+

power supply

MODBUS

D0

D1

IS GND

USB

1

2

3

13

45

2o

ff

on

( )

(

)

(-)

(-)

+8

+30 Vdc

to

GND

1 +SV

RS

485 on COM1

2 RX-

5 RXT

6 TXT

3 TX-

4 GND

7 not used

8 not used

Fig. 32: Connection of VEGAPULS 65 to RTU Bristol ControlWave Micro
1 VEGAPULS 65

2 RTU Bristol ControlWave Micro

3 Voltage supply

Parameter

Parameter

Value

Baud Rate

9600

Floating Point Format Code

2 (FC4)

RTU Data Type

32-bit registers as 2 16-bit registers

Input Register Base Number

1

The basic number of the input registers is always added to the input register address of VEGAPULS

65.
Address 1303 must hence be entered as register address for 1302 for RTU Bristol ControlWave

Micro.

Advertising