6 abb total flow, Wiring plan, Parameter – VEGA VEGAPULS 65 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol User Manual

Page 66

Advertising
background image

66

11 Supplement

VEGAPULS 65 • Modbus and Levelmaster protocol

41365-EN-121011

11.6 ABB Total Flow

Wiring plan

+

+

power supply

MODBUS

D0

D1

IS GND

USB

1

2

13

45

2o

ff

on

( )

(

)

(-)

(-)

8

1

2

6

7

Bus +

Bus -

GND

VBAT

Fig. 30: Connection of VEGAPULS 65 to RTU ABB Total Flow
1 VEGAPULS 65

2 RTU ABB Total Flow

Parameter

Parameter

Value

Baud Rate

9600

Floating Point Format Code

0

RTU Data Type

16 Bit Modicon

Input Register Base Number

1

The basic number of the input registers is always added to the input register address of VEGAPULS

65.
Address 1303 must hence be entered as register address for 1302 for RTU ABB Total Flow.

Advertising