11 Supplement
VEGAPULS 65 • Modbus and Levelmaster protocol
41365-EN-121011
11.6 ScadaPack
Wiring plan
+
+
power supply
MODBUS
D0
D1
IS GND
USB
1
3
2
13
45
5
2
1
3
4
9
6
7
8
2o
ff
on
( )
(
)
(-)
(-)
+8
+30 Vdc
to
GND
COM Part 3 (C3)
RS485
TXD-
TXD+
GND
Fig. 33: Connection of VEGAPULS 65 to RTU ScadaPack
1 VEGAPULS 65
2 RTU ScadaPack
3 Voltage supply
Parameter
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
Floating Point
Input Register Base Number
30001
The basic number of the input registers is always added to the input register address of VEGAPULS
65.
Address 31303 must hence be entered as register address for 1302 for RTU ScadaPack.