11 Supplement

VEGAPULS 68 • Modbus and Levelmaster protocol

41370-EN-121011

Input variable
Measured variable

The measured quantity is the distance between process

fitting of the sensor and product surface. The reference

plane is the seal surface on the hexagon or the lower

side of the flange.

3

4

2

1

Fig. 49: Data of the input variable
1 Reference plane

2 Measured variable, max. measuring range

3 Antenna length

4 Useful measuring range

Max. measuring range

75 m (246.1 ft)

Recommended meas. range depending on the antenna diameter

Ʋ ø 40 mm (1.575 in)

up to 15 m (49.21 ft)

Ʋ ø 48 mm (1.89 in)

up to 20 m (65.62 ft)

Ʋ ø 75 mm (2.953 in)

up to 40 m (131.2 ft)

Ʋ ø 95 mm (3.74 in)

up to 50 m (164 ft)

Ʋ Parabolic antenna

up to 75 m (246.1 ft)

Output variable
Output

Ʋ Physical layer

Digital output signal according to standard EIA-485

Ʋ Bus specifications

Modbus Application Protocol V1.1b, Modbus over serial

line V1.02

Ʋ Protocols

Modbus RTU, Modbus ASCII, Levelmaster

Max. transmission rate

9.6 Kbit/s

Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Installation reference conditions