4 modbus rtu commands, 4 fc3 read holding register, 4 fc4 read input register – VEGA VEGAPULS 68 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol User Manual

Page 71: 4 fc6 write single register

Advertising
background image

71

11 Supplement

VEGAPULS 68 • Modbus and Levelmaster protocol

41370-EN-121011

Unit Code

Measurement Unit

111

Cubic Yards

112

Cubic Feet

113

Cubic Inches

11.4 Modbus RTU commands

11.4 FC3 Read Holding Register

With this command, any number (1-127) of holding registers can be read out. The start register,

from which the readout should start, and the number of registers are transmitted.
Request:

Parameter

Length

Code/Data

Function Code

1 Byte

0x03

Start Address

2 Bytes

0x0000 to 0xFFFF

Number of Registers

2 Bytes

1 to 127 (0x7D)

Response:

Parameter

Length

Code/Data

Function Code

1 Byte

0x03

Start Address

2 Bytes

2*N

Register Value

N*2 Bytes

Data

11.4 FC4 Read Input Register

With this command, any number (1-127) of input registers can be read out. The start register, from

which the readout should start, and the number of registers are transmitted.
Request:

Parameter

Length

Code/Data

Function Code

1 Byte

0x04

Start Address

2 Bytes

0x0000 to 0xFFFF

Number of Registers

N*2 Bytes

1 to 127 (0x7D)

Response:

Parameter

Length

Code/Data

Function Code

1 Byte

0x04

Start Address

2 Bytes

2*N

Register Value

N*2 Bytes

Data

11.4 FC6 Write Single Register

With this function code an individual holding register can be written.
Request:

Parameter

Length

Code/Data

Function Code

1 Byte

0x06