4 modbus rtu commands, 4 fc3 read holding register, 4 fc4 read input register – VEGA VEGAPULS 68 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol User Manual
Page 71: 4 fc6 write single register
71
11 Supplement
VEGAPULS 68 • Modbus and Levelmaster protocol
41370-EN-121011
Unit Code
Measurement Unit
111
Cubic Yards
112
Cubic Feet
113
Cubic Inches
11.4 Modbus RTU commands
11.4 FC3 Read Holding Register
With this command, any number (1-127) of holding registers can be read out. The start register,
from which the readout should start, and the number of registers are transmitted.
Request:
Parameter
Length
Code/Data
Function Code
1 Byte
0x03
Start Address
2 Bytes
0x0000 to 0xFFFF
Number of Registers
2 Bytes
1 to 127 (0x7D)
Response:
Parameter
Length
Code/Data
Function Code
1 Byte
0x03
Start Address
2 Bytes
2*N
Register Value
N*2 Bytes
Data
11.4 FC4 Read Input Register
With this command, any number (1-127) of input registers can be read out. The start register, from
which the readout should start, and the number of registers are transmitted.
Request:
Parameter
Length
Code/Data
Function Code
1 Byte
0x04
Start Address
2 Bytes
0x0000 to 0xFFFF
Number of Registers
N*2 Bytes
1 to 127 (0x7D)
Response:
Parameter
Length
Code/Data
Function Code
1 Byte
0x04
Start Address
2 Bytes
2*N
Register Value
N*2 Bytes
Data
11.4 FC6 Write Single Register
With this function code an individual holding register can be written.
Request:
Parameter
Length
Code/Data
Function Code
1 Byte
0x06