6 bristol controlwave micro, Wiring plan, Parameter – VEGA VEGAPULS 68 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol User Manual
Page 80
Advertising
80
11 Supplement
VEGAPULS 68 • Modbus and Levelmaster protocol
41370-EN-121011
11.6 Bristol ControlWave Micro
Wiring plan
+
+
power supply
MODBUS
D0
D1
IS GND
USB
1
2
3
13
45
2o
ff
on
( )
(
)
(-)
(-)
+8
+30 Vdc
to
GND
1 +SV
RS
485 on COM1
2 RX-
5 RXT
6 TXT
3 TX-
4 GND
7 not used
8 not used
Fig. 55: Connection of VEGAPULS 68 to RTU Bristol ControlWave Micro
1 VEGAPULS 68
2 RTU Bristol ControlWave Micro
3 Voltage supply
Parameter
Parameter
Value
Baud Rate
9600
Floating Point Format Code
2 (FC4)
RTU Data Type
32-bit registers as 2 16-bit registers
Input Register Base Number
1
The basic number of the input registers is always added to the input register address of VEGAPULS
68.
Address 1303 must hence be entered as register address for 1302 for RTU Bristol ControlWave
Micro.
Advertising