VEGA VEGABOX 03 User Manual

Page 15

Advertising
background image

15

5 Connecting to the sensor

VEGABOX 03 •

45925-EN-131119

2

3

4

+

1

Fig. 10: Wiring plan VEGABOX 03 for VEGAWELL 52 4 … 20 mA/HART Pt 100
1 To the sensor

2 To power supply or the processing system

3 Connection lines resistance thermometer Pt 100

4 Shielding

2)

Wire number

Wire colour/Polarity

Function

1

brown (+)

Power supply/signal

pressure transmitter

2

blue (-)

Power supply/signal

pressure transmitter

3

White

Power supply Pt 100

4

Yellow

Measurement Pt 100

5

Red

Measurement Pt 100

6

Black

Power supply Pt 100

Shielding

Grounding

2
3

+

1

-

Fig. 11: Wiring plan VEGABOX 03 for VEGAPULS WL 61
1 To the sensor

2 To power supply or the processing system

3 Shielding

3)

Wire number

Wire colour/Polarity

Terminal

1

brown (+)

1

2

blue (-)

2

Wiring plan - VE-

GAWELL 52 4 … 20 mA/

HART Pt 100

Wiring plan - VE-

GAPULS WL 61

2)

Connect screen to ground terminal. Connect ground terminal on the outside

of the housing to ground as prescribed. The two terminals are galvanically

connected.

3)

Connect screen to ground terminal. Connect ground terminal on the outside

of the housing to ground as prescribed. The two terminals are galvanically

connected.