9 diagnostics and service, 1 maintenance, 2 status messages – VEGA SOLITRAC 31 4 … 20 mA_HART - four-wire With SIL qualification User Manual

Page 63

Advertising
background image

63

9 Diagnostics and service

SOLITRAC 31 • 4 … 20 mA/HART - four-wire

43387-EN-131119

9 Diagnostics and service

9.1 Maintenance

If the device is used correctly, no maintenance is required in normal

operation.
The corresponding source container must be checked in regular

intervals. You can find further information in the operating instructions

manual of the source container.

9.2 Status messages

The instrument features self-monitoring and diagnostics according

to NE 107 and VDI/VDE 2650. In addition to the status messages in

the following tables there are more detailed error messages available

under the menu item "Diagnostics" via the display and adjustment

module, PACTware/DTM and EDD.

The status messages are divided into the following categories:

Failure

Function check

Out of specification

Maintenance requirement

and explained by pictographs:

4

1

2

3

Fig. 21: Pictographs of the status messages
1 Failure - red

2 Out of specification - yellow

3 Function check - orange

4 Maintenance - blue

Failure: Due to a malfunction in the instrument, a failure message is

outputted.
This status message is always active. It cannot be deactivated by the

user.
Function check: The instrument is in operation, the measured value

is temporarily invalid (for example during simulation).
This status message is inactive by default. It can be activated by the

user via PACTware/DTM or EDD.
Out of specification: The measured value is unstable because the

instrument specification is exceeded (e.g. electronics temperature).
This status message is inactive by default. It can be activated by the

user via PACTware/DTM or EDD.

Status messages

Advertising