3 Product description

SOLITRAC 31 • 4 … 20 mA/HART - four-wire

43387-EN-131119

Modification status electronics from -07

The instrument is available in different electronics versions. Each ver-

sion can be identified via the product code on the type label:

Standard electronics type PT30E-XX

The scope of delivery encompasses:

Radiation-based sensor

Mounting accessory

Documentation

– this operating instructions manual

– Safety Manual (SIL) PROTRAC series 30 (Document-ID 42961)

– Operating instructions manual "Display and adjustment mod-

ule" (optional)

– Ex-specific "Safety instructions" (with Ex versions)

– if necessary, further certificates

3.2 Principle of operation

The instrument is suitable for applications in liquids and bulk solids in

vessels under difficult process conditions. There are application pos-

sibilities in nearly all areas of industry.
The level is detected contactlessly right through the vessel wall.

Neither a process fitting nor a vessel opening are required. The instru-

ment is thus ideal for retro installation.

In radiation-based measurement, a Caesium-137 or Cobalt-60 iso-

tope emits focussed gamma rays that are attenuated when penetrat-

ing the vessel wall and the medium. The PVT detector on the opposite

side of the tank receives the radiation, whose strength is dependent

on the level. The measuring principle has proven to be very reliable

in conjunction with extreme process conditions because it measures

contactlessly from outside through the vessel wall. The measuring

system ensures maximum safety, reliability and plant availability,

independently of the medium and its properties.

3.3 System limitations

There are several measuring principle-specific factors which can influ-

ence the measuring result. Keep these factors in mind in order to fully

utilize the capabilities of the instrument with respect to measurement

certainty and reproducibility.

The implemented radioactive isotope and its activity must be selected

according to the properties of the vessel and the medium. The neces-

sary radioactive activity must be calculated on the basis of the plant

data.
To this end, make use of our planning service for an optimum layout of

the measurement and selection of the isotope. This applies particu-

larly to SIL applications.

Electronics versions

Scope of delivery

Application area

Functional principle

Activity of the source