3 5–fold valve block, 3 5-fold valve block – VEGA Mounting accessories, pressure measurement technology User Manual

Page 19

Advertising
background image

Feature

Feature

Series

3-fold valve block, flanging

Input (process)

½ NPT

Output (differential pressure transmit-
ter)

Flange according to EN 61518

Ventilation holes

¼ NPT

Pressure stage/Max. permissible
pressure

PN 420/420 bar

Max. permissible pressure at 80 °C

420 bar

Max. permissible pressure at 250 °C

300 bar

Temperature max.

250 °C

Weight

approx. 2.6 kg

6

.3 5-fold valve block

The 5-fold valve block is used for more sophisticated applications. It
has the following functions:

l

Separation from the process

l

Pressure equalisation of the measuring chambers of the differ-
ential pressure transmitter

l

Blowing out/Testing

The mounting is carried out via integrated threaded connections and a
bracket existing on site.

Application area/Func-
tion

Installation

Mounting accessories, pressure measurement technology

19

6 Valve blocks

43478

-

EN

-121018