Cooling zones
4
.1 Siphons
Siphons according to DIN 16282 are a cooling zone for protection of
the pressure transmitters against too hot process media. Through
condensation in the elbow pipe, a protective water accumulation is
formed. Even in applications with hot steam, a medium temperature
<
100 °C on the transmitter is ensured.
There are two different series of siphons: the u-form for horizontal
pressure extraction or the circular form for vertical pressure extraction.
Depending on the material, there is a different pressure/temperature
derating (see "Technical data").
G ½
180 mm (7.09")
56 mm
(2.21")
200 mm (7.87")
155 mm (6.10")
ø 6 mm
(0.24")
145 mm (5.71")
G ½
1
2
Fig. 1: Configuration of siphon according to DIN 16282, Form A (U-form) for
horizontal pressure extraction
1
Input
2
Output
Application area
Configuration