24

5 Connecting to power supply and bus system

VEGAPULS 66 • Modbus and Levelmaster protocol

41366-EN-121011

The connection to the indicating and adjustment module or to the

interface adapter is carried out via contact pins in the housing.
Information:

The terminal block is pluggable and can be removed from the elec-

tronics. To do this, lift the terminal block with a small screwdriver and

pull it out. When inserting the terminal block again, you should hear it

snap in.

Proceed as follows:
1. Unscrew the housing cover
2. If an indicating and adjustment module is installed, remove it by

turning it slightly to the left.

3. Loosen compression nut of the cable entry
4. Remove approx. 10 cm (4 in) of the cable mantle, strip approx.

1 cm (0.4 in) of insulation from the ends of the individual wires

5. Insert the cable into the sensor through the cable entry

Fig. 18: Connection steps 5 and 6

6. Insert the wire ends into the terminals according to the wiring plan
Information:

Solid cores as well as flexible cores with cable end sleeves are

inserted directly into the terminal openings. In case of flexible cores

without end sleeves, press the terminal head with a small screwdriver;

the terminal opening is freed. When the screwdriver is released, the

terminal closes again.
You can find further information to the max. wire cross-section under

"Technical data/Electromechanical data"
7. Check the hold of the wires in the terminals by lightly pulling on

them

8. Connect the screen to the internal ground terminal, connect the

outer ground terminal to potential equalisation

9. Tighten the compression nut of the cable entry. The seal ring must

completely encircle the cable

Connection procedure