6 configuration of typical modbus hosts, 5 error codes, 6 fisher roc 809 – VEGA VEGAPULS 66 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol User Manual
Page 72: Wiring plan, Parameter
72
11 Supplement
VEGAPULS 66 • Modbus and Levelmaster protocol
41366-EN-121011
Response:
Parameter
Length
Code/Data
Report Receive to Transmit Delay
7 characters ASCII
UuuRmmm
mmm = milliseconds (50 bis 250),
default = 127 ms
11.5 Error codes
Error Code
Name
EE-Error
Error While Storing Data in EEPROM
FR-Error
Erorr in Frame (to short, to long, wrong data)
LV-Error
Value out of limits
11.6 Configuration of typical Modbus hosts
11.6 Fisher ROC 809
Wiring plan
+
+
power supply
MODBUS
D0
D1
IS GND
USB
B
COM
Z
Y
A
(Rx/Tx -)
(Rx/Tx +)
1
2
3
13
45
2o
ff
on
( )
(
)
(-)
(-)
+8
+30 Vdc
to
GND
Fig. 47: Connection of VEGAPULS 66 to RTU Fisher ROC 809
1 VEGAPULS 66
2 RTU Fisher ROC 809
3 Voltage supply
Parameter
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
Conversion Code 66
Input Register Base Number
0
The basic number of the input registers is always added to the input register address of VEGAPULS