6 configuration of typical modbus hosts, 5 error codes, 6 fisher roc 809 – VEGA VEGAPULS 66 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol User Manual

Page 72: Wiring plan, Parameter

Advertising
background image

72

11 Supplement

VEGAPULS 66 • Modbus and Levelmaster protocol

41366-EN-121011

Response:

Parameter

Length

Code/Data

Report Receive to Transmit Delay

7 characters ASCII

UuuRmmm
mmm = milliseconds (50 bis 250),

default = 127 ms

11.5 Error codes

Error Code

Name

EE-Error

Error While Storing Data in EEPROM

FR-Error

Erorr in Frame (to short, to long, wrong data)

LV-Error

Value out of limits

11.6 Configuration of typical Modbus hosts

11.6 Fisher ROC 809

Wiring plan

+

+

power supply

MODBUS

D0

D1

IS GND

USB

B

COM

Z

Y

A

(Rx/Tx -)

(Rx/Tx +)

1

2

3

13

45

2o

ff

on

( )

(

)

(-)

(-)

+8

+30 Vdc

to

GND

Fig. 47: Connection of VEGAPULS 66 to RTU Fisher ROC 809
1 VEGAPULS 66

2 RTU Fisher ROC 809

3 Voltage supply

Parameter

Parameter

Value

Baud Rate

9600

Floating Point Format Code

0

RTU Data Type

Conversion Code 66

Input Register Base Number

0

The basic number of the input registers is always added to the input register address of VEGAPULS