5 report unit number, 5 assign unit number, 5 set number of floats – VEGA VEGAPULS 66 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol User Manual

Page 70

Advertising
background image

70

11 Supplement

VEGAPULS 66 • Modbus and Levelmaster protocol

41366-EN-121011

Response:

Parameter

Length

Code/Data

Report Level (and Temperature)

24 characters ASCII

UuuDlll.llFtttEeeeeWwwww
uu = Address
lll.ll = PV in inches
ttt = Temperature in Fahrenheit
eeee = Error number (0 no error, 1

level data not readable)
wwww = Warning number (0 no

warning)

Level in inches is repeated for sensors with 2 levels. PV value is transmitted as first measured value,

SV as second measured value.
PV, SV, TV and QV can be adjusted via the sensor DTM.

11.5 Report Unit Number

Request:

Parameter

Length

Code/Data

Report Unit Number

5 characters ASCII

U**N?

Response:

Parameter

Length

Code/Data

Report Level (and Temperature)

6 characters ASCII

UuuNnn

11.5 Assign Unit Number

Request:

Parameter

Length

Code/Data

Assign Unit Number

6 characters ASCII

UuuNnn

Response:

Parameter

Length

Code/Data

Assign Unit Number

6 characters ASCII

UuuNOK
uu = new Address

11.5 Set number of Floats

Request:

Parameter

Length

Code/Data

Set number of Floats

5 characters ASCII

UuuFn

Response:

Parameter

Length

Code/Data

Set number of Floats

6 characters ASCII

UuuFOK

If the number is set to 0, no level is returned