VEGA VEGAFLEX 86 Modbus and Levelmaster protocol User Manual

Page 18

Advertising
background image

18

4 Mounting

VEGAFLEX 86 • Modbus and Levelmaster protocol

41848-EN-130314

sible. The exact value of the min. distance (lower dead band) is stated

in chapter "Technical data".

Fig. 8: Vessel with conical bottom

Plastic vessel/Glass vessel

The guided microwave principle requires a metal surface on the pro-

cess fitting. Therefore use in plastic vessels etc. an instrument version

with flange (from DN 50) or place a metal sheet (ø > 200 mm/8 in)

beneath the process fitting when screwing it in.
Make sure that the plate has direct contact with the process fitting.
When installing rod or cable probes in vessels without metal walls,

e.g. in plastic vessels, the measured value can be influenced by

strong electromagnetic fields (emitted interference according to

EN 61326: class A). In this case, use a probe with coaxial version.

1

2

Fig. 9: Installation in non-metal vessel
1 Flange

2 Metal sheet

Type of vessel

Advertising