11 Supplement

VEGAFLEX 86 • Modbus and Levelmaster protocol

41848-EN-130314

11.6 Configuration of typical Modbus hosts

Fisher ROC 809

Wiring plan

+

+

power supply

MODBUS

D0

D1

IS GND

USB

B

COM

Z

Y

A

(Rx/Tx -)

(Rx/Tx +)

1

2

3

13

45

2o

ff

on

( )

(

)

(-)

(-)

+8

+30 Vdc

to

GND

Fig. 49: Connection of VEGAFLEX 86 to RTU Fisher ROC 809
1 VEGAFLEX 86

2 RTU Fisher ROC 809

3 Voltage supply

Parameter

Parameter

Value

Baud Rate

9600

Floating Point Format Code

0

RTU Data Type

Conversion Code 66

Input Register Base Number

0

The basic number of the input registers is always added to the input register address of VEGAFLEX

86.
Address 1300 must hence be entered as register address for RTU Fisher ROC 809.