4 spacers - metal (m1, m2, m3, m4) – VEGA VEGAFLEX series 80 Centering User Manual

Page 13

Advertising
background image

13

2 Mounting

Centering • for VEGAFLEX series 80

44967-EN-131119

Note:

The spacer may not be moved in the axial direction. The insulation of

the cable or rod could be damaged. You can remove the spacer later-

ally and attach it again at another position.

2.4 Spacers - Metal (M1, M2, M3, M4)

2

2

1

Fig. 10: Mounting the spacer
1 Spacer (M1, M2, M3, M4)

M1, M3 - outer ø 49.2 up to 56.3 mm (1.9 up to 2.2 in)

M2, M4 - outer ø 66.6 up to 84.9 mm (2.6 up to 3.3 in)

2 Retaining ring

1. The spacer should be mounted at the lower end of the probe rod.
2. Slide the retaining ring (2) onto the rod of the probe.

Tip:

Wear gloves when sliding the parts onto the rod or use a piece of thin

tubing
If you have shortened the probe, it is helpful to slightly chamfer the

end of the rod.
3. Slide the spacer (1) with open elastic arms upward and an ad-

ditional retaining ring (2) onto the rod of the probe.
The retaining rings fix the spacer in the requested position.