17

5 Connecting to power supply

VEGASWING 66 • - Relay

44950-EN-130805

5 Connecting to power supply

5.1 Preparing the connection

Always keep in mind the following safety instructions:

Connect only in the complete absence of line voltage

In hazardous areas you must take note of the respective regulations,

conformity and type approval certificates of the sensors and power

supply units.

Connect the operating voltage according to the connection diagrams.

The electronics module with relay output is designed in protection

class I. To maintain this protection class, it is absolutely necessary

that the earth conductor be connected to the inner earth conductor

terminal. Keep the general installation regulations in mind. Take note

of the corresponding installation regulations for hazardous areas with

Ex applications.
The data for power supply are specified in chapter "Technical data".

The instrument is connected with standard three-wire cable without

screen. If electromagnetic interference is expected which is above the

test values of EN 61326 for industrial areas, screened cable should

be used.
Use cable with round cross section for instruments with housing and

cable gland. To ensure the seal effect of the cable gland (IP protection

rating), find out which cable outer diameter the cable gland is suitable

for.

5 … 9 mm (0.20 … 0.35 in)

6 … 12 mm (0.24 … 0.47 in)

10 … 14 mm (0.40 … 0.55 in)

Use a cable gland fitting the cable diameter.
In hazardous areas, only use approved cable connections for VEGAS-

WING 66.

Take note of the corresponding installation regulations for Ex applica-

tions.
Cover all housing openings conforming to standard according to

EN 60079-1.

5.2 Connection procedure

With Ex instruments, the housing cover may only be opened if there is

no explosive atmosphere present.
Proceed as follows:
1. Unscrew the housing cover
2. Loosen compression nut of the cable entry
3. Remove approx. 10 cm (4 in) of the cable mantle, strip approx.

1 cm (0.4 in) of insulation from the ends of the individual wires

4. Insert the cable into the sensor through the cable entry

Note safety instructions

Take note of safety

instructions for Ex

applications

Voltage supply

Connection cable

Connection cable

for Ex applications