4 proof test – VEGA VEGASWING 66 - Relay With SIL qualification User Manual

Page 23

Advertising
background image

23

6 Setup

VEGASWING 66 • - Relay

44950-EN-130805

Level

Switching sta-

tus

Signal lamp -

green
Voltage supply

Signal lamp -

yellow
Switching sta-

tus

Signal lamp

- red
Fault message

Mode max.
Overflow pro-

tection

5

3

4

(8)

(6) (7)

Relay deener-

gized

Mode min.
Dry run protec-

tion

5

3

4

(8)

(6) (7)

Relay energized

Mode min.
Dry run protec-

tion

5

3

4

(8)

(6) (7)

Relay deener-

gized

Failure of the

supply voltage
(max./min. mode)

any

5

3

4

(8)

(6) (7)

Relay deener-

gized

Fault

any

5

3

4

(8)

(6) (7)

Relay deener-

gized

6.4 Proof test

To find out possible undetected, dangerous failures, a proof test must

be carried out in adequate time intervals to check the safety function.

It is the user's responsibility to choose the type of testing.
You will find further instructions in the Safety Manual.
The following options are available for carrying out the proof test:
1. Short interruption of the supply line to the sensor

Average coverage (detected errors)

2. Dismounting of the sensor and immersion in the original medium

High coverage (detected errors)

3. Filling of the vessel up to the switching point

High coverage (detected errors)