VEGA VEGASWING 66 - Relay With SIL qualification User Manual

Page 19

Advertising
background image

19

5 Connecting to power supply

VEGASWING 66 • - Relay

44950-EN-130805

7

4

6

1

5

3

2

on

g / cm3

0,7

min

max

0,5

R

Fig. 12: Electronics and connection compartment, single chamber housing
1 Control lamp - fault indication (red)

2 Signal lamp - Switching condition (yellow)

3 Signal lamp - Operating condition (green)

4 Mode switch for selecting the switching behaviour (min./max.)

5 DIL switch for sensitivity adjustment

6 Ground terminal

7 Connection terminals

We recommend connecting VEGASWING 66 according to the closed

circuit principle, i.e. the switching circuit is open when there is a level

signal, line break or fault (safe condition).
Information:

The relays (2 x SPDT) are always shown in non-operative condition.

1

2

3

+

L1

-

N

1 2

3 4 5 6 7 8

Fig. 13: Wiring plan, single chamber housing
1 Voltage supply

2 Relay output SPDT

3 Relay output SPDT

Electronics and connec-

tion compartment

Wiring plan