4 parameter adjustment - density measurement – VEGA MINITRAC 31 Foundation Fieldbus User Manual

Page 34

Advertising
background image

34

6 Set up with the display and adjustment module

MINITRAC 31 • Foundation Fieldbus

41782-EN-131119

Menu

Menu item

Default value

Setup

Measurement loop name

Sensor

Isotope

Cs-137

Application

Level

Background radiation

0 ct/s

Unit of the process value

%

Temperature unit

° C

Adjustment min.

Min. process value = 0 %

Adjustment max.

Max. process value = 100 %

Linearization

0 ct/s = 100 %
90000 ct/s = 0 %

Damping

60 s

Real value correction

0

Mode

Overfill protection

Upper switching point - Pro-

cess value

0 %

Lower switching point - Pro-

cess value

0 %

Upper switching point - Tem-

perature

50 °C

Upper switching point - Tem-

perature

25 °C

Reference value - Relay

None

Block adjustment

Released

Address - Summation Slave free

Display

Language

Selected language

Displayed value

Pulse rate

Display unit

ct/s

Additional ad-

justments

Temperature unit

°C

Linearisation curve

Empty

HART mode

Standard
Address 0

6.4 Parameter adjustment - Density

measurement

The instrument is adapted to the application conditions via the pa-

rameter adjustment. The parameter adjustment is carried out with an

adjustment menu.
Information:

In this operating instructions manual, the instrument-specific param-

eters are described. Further general parameters are described in the

operating instructions manual "Display and adjustment module".