6 Set up with the display and adjustment module

MINITRAC 31 • Foundation Fieldbus

41782-EN-131119

You have to enter the address of the Slave instrument in the list of

the Master instrument. This function is not possible in the display and

adjustment module. To do this you need PACTware with the respective

DTM.

The main menu is divided into five sections with the following func-

tions:

Setup: Settings, e.g. for measurement loop name, isotope, applica-

tion, background radiation, adjustment, signal output
Display: Settings, for example language, measured value display
Diagnosis: Information, for example, of device status, peak value,

simulation
Additional adjustments: Instrument unit, reset, date/time, copying

function
Info: Instrument name, hardware and software version, date of manu-

facture, instrument features

Check if the correct language is already set for the display. If not, you

can change the language in the menu item "Display/Language".

Start with the setup of MINITRAC 31.
In the main menu point "Setup", the individual submenu points

should be selected one after the other and provided with the correct

parameters to ensure optimum adjustment of the measurement. The

procedure is described in the following.
Stick with the normal sequence of the menu items as closely as pos-

sible.
Setup
In this menu item you can adjust the MINITRAC 31 to the integrated

isotope in the source container.
For this purpose, check which isotope is integrated in the source

container. You can find this information on the type label of the source

container.

With this selection, the sensitivity of the sensor is adapted in an opti-

mum way to the isotope.

Main menu

Procedure

Setup - Isotope