8 Diagnosis, asset management and service

VEGABAR 82 • 4 … 20 mA

45027-EN-131010

F

T

: Thermal change of zero signal and output span

F

Kl

: Deviation

F

a

: Thermal change of the current output

You can find the specifications in chapter "Technical data".

Pressure measurement in the pipeline 8 bar (800 KPa)
Product temperature up to 50 °C
VEGABAR 82 with measuring range 10 bar, deviation < 0.075 %
Calculation of the set Turn Down: TD = 10 bar/8 bar, TD = 1.25
1. step: Calculation of the basic accuracy

F

perf

= √((F

T

)

2

+ (F

Kl

)

2

+ (F

a

)

2

)

F

T

= (0.15 %) x (0.5 + 0.5 x TD)

F

Kl

= 0.075 %

F

a

= 0.15 %

F

perf

= √((0.15 %) x (0.5 + 0.5 x TD)

2

+ (0.075 %)

2

) + (0.15 %)

2

)

F

perf

= 0.24 %

Step 2: Calculation of the total deviation

F

total

= F

perf

+ F

stab

F

stab

= (0.05 % x TD)/year

F

stab

= (0.05 % x 1.25)/year

F

stab

= 0.06 %

F

total

= 0.24 % + 0.06 % = 0.30 %

8.6 Exchange process assembly with version

IP 68 (25 bar)

With version IP 68 (25 bar), the user can exchange the process as-

sembly on site. Connection cable and external housing can be kept.
Required tools:

Hexagon socket wrench, size 2

Caution:

The exchange may only be carried out in the complete absence of

line voltage.
In Ex applications, only a replacement part with appropriate Ex ap-

proval may be used.
Proceed as follows when carrying out the exchange:
1. Losen the fixing screw with the hexagon socket wrench
2. Carefully detach the cable assembly from the process assembly

Practical example

Calculation

Advertising