3 Product description

VEGABAR 82 • 4 … 20 mA

45027-EN-131010

Sensor element is the CERTEC

®

measuring cell with robust ceramic

diaphragm. The process pressure deflects the ceramic diaphragm

and causes a capacitance change in the measuring cell. This capaci-

tance change is converted into an electrical signal and outputted as

measured value via the output signal.
The CERTEC

®

measuring cell is available in two sizes:

ø 17.5 mm with small process fittings

ø 28 mm with large process fittings as well as all flange connec-

tions

The measuring cell design depends on the selected pressure type.

Relative pressure: the measuring cell is open to atmosphere. The

ambient pressure is detected in the measuring cell and compensated.

It thus has no influence on the measured value.
Absolute pressure: the measuring cell is evacuated and encapsu-

lated. The ambient pressure is not compensated and does hence

influence the measured value.
Relative pressure, climate-compensated: the measuring cell is

evacuated and encapsulated. The ambient pressure is detected

through a reference sensor in the electronics and compensated. It

thus has no influence on the measured value.

The following presentations show the installation of the CERTEC

®

measuring cell into the process fitting and the different seal concepts.

1

2

4

5

3

Fig. 3: Recessed installation of the CERTEC

®

measuring cell

1 Measuring cell

2 Seal for the measuring cell

3 Diaphragm

4 Process fitting

5 Seal for the process fitting

Measuring system

Pressure types

Seal concepts

Recessed installation