4 Mounting

VEGAFLEX 83 • 4 … 20 mA/HART two-wire

41834-EN-130612

If possible, avoid sockets. Mount the sensor flush with the vessel top.

If this is not possible, use short sockets with small diameter.
Higher sockets or sockets with a bigger diameter can generally be

used. They can, however, increase the upper blocking distance (dead

band). Check if this is relevant for your measurement.
In such cases, always carry out a false signal suppression after instal-

lation. You can find further information under "Setup procedure".

h

d

d

h

DN40 ... DN150

> DN150 ... DN200

150
100

_<
_<

Fig. 9: Mounting socket

When welding the socket, make sure that the socket is flush with the

vessel top.

1

2

Fig. 10: Socket must be installed flush
1 Unfavourable installation

2 Socket flush - optimum installation

Before beginning the welding work, remove the electronics module

from the sensor. By doing this, you avoid damage to the electronics

through inductive coupling.

Socket

Welding work