VEGA VEGAFLEX 83 4 … 20 mA_HART two-wire PFA insulated User Manual

Page 52

Advertising
background image

52

6 Set up with the display and adjustment module

VEGAFLEX 83 • 4 … 20 mA/HART two-wire

41834-EN-130612

Menu item

Default value

Modified value

Current output - Max.

20.5 mA

Current output 2 - Output variable
Second HART variable (SV)

Distance - Level

Current output 2 - Output characteristics

0 … 100 % correspond to

4 … 20 mA

Current output 2 - Reaction in case of failure

≤ 3.6 mA

Current output - Min.

3.8 mA

Current output - Max.

20.5 mA

Third HART variable (TV)

Measurement certainty, level

Fourth HART variable (QV)

Electronics temperature

Display

Menu item

Default value

Modified value

Language

Order-specific

Displayed value 1

Filling height Level

Displayed value 2

Electronics temperature

Backlight

Switched off

Diagnostics

Menu item

Default value

Modified value

Status signals - Function control

Switched on

Status signals - Out of specification

Switched off

Status signals - Maintenance

Switched off

Device memory - Echo curve memory

Stopped

Device memory - Measured value memory

Started

Device memory - Measured value memory -

Measured values

Distance level, percentage value

level, reliability level, electronics

temperature

Device memory - Measured value memory - Re-

cording in time interval

3 min.

Device memory - Measured value memory - Re-

cording with measured value difference

15 %

Device memory - Measured value memory - Start

with measured value

Not active

Device memory - Measured value memory - Stop

with measured value

Not active

Device memory - Measured value memory - Stop

recording when memory is full

Not active

Advertising