6 Set up with the display and adjustment module

VEGAFLEX 83 • 4 … 20 mA/HART two-wire

41834-EN-130612

Adjust the requested percentage value with [+] and store with [OK].

Enter the appropriate distance value in m (corresponding to the

percentage value) for the full vessel. The distance refers to the sensor

reference plane (seal surface of the process fitting). Keep in mind that

the max. level must lie below the dead band.

In this menu item you can enter the min. adjustment for the level. With

interface measurement this is the minimum total level.

Adjust the requested percentage value with [+] and store with [OK].

Enter the suitable distance value in m for the empty vessel (e.g.

distance from the flange to the probe end) corresponding to the per-

centage value. The distance refers tot he sensor reference plane (seal

surface of the process fitting).

This menu item is only available if you have selected interface meas-

urement under the menu item "Application".

You can accept the adjustment of the level measurement also for the

interface measurement. If you select "Yes", the current setting will be

displayed.

Setup - Min. adjustment

Level

Setup - Max. adjustment -

Interface