VEGA VEGAFLEX 83 4 … 20 mA_HART two-wire Rod probe - Polished version With SIL qualification User Manual

Page 65

Advertising
background image

65

10 Diagnostics and service

VEGAFLEX 83 • 4 … 20 mA/HART two-wire

44225-EN-130823

Failure: Due to a malfunction in the instrument, a failure message is

outputted.
This status message is always active. It cannot be deactivated by the

user.
Function check: The instrument is in operation, the measured value

is temporarily invalid (for example during simulation).
This status message is inactive by default. It can be activated by the

user via PACTware/DTM or EDD.
Out of specification: The measured value is unstable because the

instrument specification is exceeded (e.g. electronics temperature).
This status message is inactive by default. It can be activated by the

user via PACTware/DTM or EDD.
Maintenance: Due to external influences, the instrument function

is limited. The measurement is affected, but the measured value is

still valid. Plan in maintenance for the instrument because a failure is

expected in the near future (e.g. due to buildup).
This status message is inactive by default. It can be activated by the

user via PACTware/DTM or EDD.

The following table shows the error codes in the status message

"Failure" and gives information on the reason and rectification. Keep

in mind that some information is only valid with four-wire instruments.

Code
Text mes-

sage

Cause

Rectification

F013
no measured

value avail-

able

– Sensor does not detect an

echo during operation

– Process component or

probe contaminated or

defective

– Check or correct installation

and/or parameter adjust-

ment

– Clean or exchange process

component or probe

F017
Adjustment

span too small

– Adjustment not within

specification

– Change adjustment accord-

ing to the limit values (dif-

ference between min. and

max. ≥ 10 mm)

F025
Error in the

linearization

table

– Index markers are not con-

tinuously rising, for examle

unlogical value pairs

– Check values of the lineari-

zation table

– Delete/create a new lineari-

zation table

F036
No operable

software

– Failed or interrupted soft-

ware update

– Repeat software update

– Check electronics version

– Exchanging the electronics

– Send instrument for repair

F040
Error in the

electronics

– Hardware defect

– Exchanging the electronics

– Send instrument for repair

F041
Probe loss

– Cable probe broken or rod

probe defective

– Check probe and exchange,

if necessary

Failure

Advertising