12 Supplement

VEGAFLEX 83 • 4 … 20 mA/HART two-wire

44225-EN-130823

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

+860 … +1060 mbar/+86 … +106 kPa

(+12.5 … +15.4 psig)

Installation reference conditions

Ʋ Min. distance to installations

> 500 mm (19.69 in)

Ʋ Vessel

metallic, ø 1 m (3.281 ft), centric installation, process

fitting flush with the vessel ceiling

Ʋ Medium

Water/Oil (dielectric constant ~2.0)

5)

Ʋ Installation

Probe end does not touch the vessel bottom

Sensor parameter adjustment

No gating out of false signals carried out

Typical deviation - Interface measure-

ment

± 5 mm (0.197 in)

Typical deviation - Total level interface

measurement

See following diagrams

Typical deviation - Level measurement

6)7)

See following diagrams

L

0

-2 mm

(-0.079

")

2 mm

(0.079

")

15 mm

(0.591

"

)

-15 mm

(-0.591

")

0,2 m

(7.874

"

)

0,08 m

(3.15

"

)

0,04 m

(1.575

")

1

Fig. 44: Deviation VEGAFLEX 83 in rod version in water
1 Dead band - no measurement possible in this area

L Probe length

5)

With interface measurement = 2.0

6)

Depending on the installation conditions, there can be deviations which can be rectified with an adaptation of

the adjustment or a change of the measured value offset in the DTM service mode

7)

The dead bands can be optimizes by a false signal suppression.