9 Diagnosis, asset management and service

VEGABAR 87 • 4 … 20 mA/HART

45044-EN-131010

Code
Text mes-

sage

Cause

Rectification

F265
Measurement

function dis-

turbed

– Sensor no longer carries

out a measurement

– Carry out a reset

– Separate operating voltage

briefly

F266
Impermissi-

ble operating

voltage

– Operating voltage below

specified range

– Check electrical connection

– if necessary, increase

operating voltage

The following table shows the error codes and text messages in the

status message "Function check" and provides information on causes

as well as corrective measures.

Code
Text mes-

sage

Cause

Rectification

C700
Simulation ac-

tive

– A simulation is active

– Finish simulation

– Wait for the automatic end

after 60 mins.

The following table shows the error codes and text messages in the

status message "Out of specification" and provides information on

causes as well as corrective measures.

Code
Text mes-

sage

Cause

Rectification

S600
Unpermissi-

ble electronics

temperature

– Temperature of the elec-

tronics in the non-specified

section

– Check ambient temperature

– Isolate electronics

– Use instrument with higher

temperature range

S603
Impermissi-

ble operating

voltage

– Operating voltage below

specified range

– Check electrical connection

– if necessary, increase

operating voltage

The following table shows the error codes and text messages in the

status message "Maintenance" and provides information on causes

as well as corrective measures.

Code
Text mes-

sage

Cause

Rectification

M500
Error in the

delivery sta-

tus

– Stored delivery status is

wrong

– Send instrument for repair

Function check

Out of specification

Maintenance