9 Diagnosis, asset management and service

VEGABAR 87 • 4 … 20 mA/HART

45044-EN-131010

F

T

: Thermal change of zero signal and output span

F

Kl

: Deviation

F

a

: Thermal change of the current output

You can find the specifications in chapter "Technical data".

Level measurement 1500 mmWs
Product temperature up to 40 °C
VEGABAR 87 with measuring range 0.2 bar
Deviation < 0.1 %
Calculation ΔT: ΔT = 40 °C - 20 °C = 20 K
Calculation of the set Turn Down:
TD = 200 mbar/147 mbar, TD = 1.4
1. step: Calculation of the basic accuracy

F

perf

= √((F

T

)

2

+ (F

Kl

)

2

)

F

T

= (0.15 %) x (0.5 + 0.5 x TD)

F

Kl

= 0.1 %

F

perf

= √((0.15 %) x (0.5 + 0.5 x TD)

2

+ (0.1 %)

2

)

F

perf

= 0.21 %

Step 2: Calculation of the total deviation

F

total

= F

perf

+ F

stab

F

stab

= (0.05 % x TD)

F

stab

= (0.05 % x 1.4)

F

stab

= 0.07 %

F

total

= 0.21 % + 0.07 % = 0.28 %

1. step: Calculation of the basic accuracy

F

perf

= √((F

T

)

2

+ (F

Kl

)

2

+ (F

a

)

2

)

F

T

= (0.15 %) x (0.5 + 0.5 x TD)

F

Kl

= 0.1 %

F

a

= 0.15 %

F

perf

= √((0.15 %) x (0.5 + 0.5 x TD)

2

+ (0.1 %)

2

+ (0.15 %)

2

)

F

perf

= 0.25 %

Step 2: Calculation of the total deviation

F

total

= F

perf

+ F

stab

F

stab

= (0.05 % x TD)

F

stab

= (0.05 % x 1.4)

F

stab

= 0.07 %

F

total

= 0.25 % + 0.07 % = 0.32 %

9.6 Exchange process assembly with version

IP 68 (25 bar)

With version IP 68 (25 bar), the user can exchange the process as-

sembly on site. Connection cable and external housing can be kept.

Practical example

Calculation - Digital out-

put signal

Calculation - Analogue

output signal