9 Diagnostics and service

VEGAFLEX 81 • 4 … 20 mA/HART two-wire

41824-EN-130612

Code
Text mes-

sage

Cause

Rectification

M505
no measured

value avail-

able

– Sensor does not detect an

echo during operation

– Check and correct instal-

lation and/or parameter

adjustment

– Process component or

probe contaminated or

defective

– Clean or exchange process

component or probe

M506
Installation/

Setup error

– Error during setup

– Check and correct instal-

lation and/or parameter

adjustment

– Check probe length

M507
Error in the

instrument

settings

– Error during setup

– Error when carrying out a

reset

– False signal suppression

faulty

– Carry out reset and repeat

setup

9.4 Rectify faults

The operator of the system is responsible for taking suitable meas-

ures to rectify faults.

The first measures are:

Evaluation of fault messages, for example via the display and

adjustment module

Checking the output signal

Treatment of measurement errors

Further comprehensive diagnostics options offer a PC with the soft-

ware PACTware and the suitable DTM. In many cases, the reasons

can be determined in this way and faults can be rectified.

Connect a multimeter in the suitable measuring range according to

the wiring plan. The following table describes possible errors in the

current signal and helps to remove them:

Error

Cause

Rectification

4 … 20 mA signal

not stable

– Level fluctua-

tions

– Set damping according to the

instrument via the display and

adjustment module or PACTware/

DTM

Reaction when malfunc-

tions occur

Procedure for fault recti-

fication

Check the 4 … 20 mA

signal