11 Supplement

VEGAFLEX 81 • 4 … 20 mA/HART two-wire

41824-EN-130612

Ʋ Cable probes

ε

r

≥ 1.6

Ʋ Rod probes

ε

r

≥ 1.6

2

4

5

3

2

4

5

3

1

1

Fig. 47: Measuring ranges - VEGAFLEX 81
1 Reference plane

2 Probe length L

3 Measuring range (default setting refers to the measuring range in water)

4 Upper dead band (see diagrams under Accuracy - grey section)

5 Lower dead band (see diagrams under Accuracy - grey section)

Output variable
Output signal

4 … 20 mA/HART

Range of the output signal

3.8 … 20.5 mA/HART (default setting)

Fulfilled HART specification

7

Signal resolution

0.3 µA

Failure signal current output (adjustable) Last valid measured value, ≥ 21 mA, ≤ 3.6 mA