Max. output current

22 mA

Starting current

3.6 mA

Load (4 … 20 mA/HART - active)

<

500 Ω

Damping (63 % of the input variable)

0 … 999 s, adjustable

HART output values

-

PV (Primary Value)

Distance to the level

-

SV (Secondary Value)

Level as percentage value

-

TV (Third Value)

Linearised percentage value

-

QV (Fourth Value)

Scaled measured value

Resolution, digital

<

1 mm (0.039 in)

Accuracy (according to DIN EN 60770-1)

Process reference conditions according to DIN EN 61298-1

-

Temperature

+

18 … +30 °C (+64 … +86 °F)

-

Relative humidity

45 … 75 %

-

Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Installation reference conditions

-

Min. distance to installations

>

200 mm (7.874 in)

-

Reflector

Corner reflector

-

False reflections

Largest false echo 20 dB smaller than the useful
echo

Deviation with liquids

See following diagrams

0,5 m (1.6 ft)

10 mm (0.394 in)

- 10 mm (- 0.394 in)

2 mm (0.079 in)

- 2 mm (- 0.079 in)

0

1 2

3

Fig. 46: Deviation under reference conditions - encapsulated antenna system

1

Reference plane

2

Antenna edge

3

Recommended measuring range