6 Set up with the display and adjustment module

VEGABAR 82 • HART and accumulator pack

45029-EN-131107

The default setting is output characteristics 4 … 20 mA, failure mode

< 3.6 mA.

In the menu item "Current output Min./Max.", you determine the reac-

tion of the current output during operation.

The default setting is min. current 3.8 mA and max. current 20.5 mA.

In the menu item "Lock/unlock adjustment", you can protect the

sensor parameters against unauthorized modification. The PIN is

activated/deactivated permanently.
The following adjustment functions are possible without entering the

PIN:

Select menu items and show data

Read data from the sensor into the display and adjustment mod-

ule.

Caution:

With active PIN, adjustment via PACTware/DTM as well as other

systems is also blocked.
You can change the PIN number under "Additional adjustments -

PIN".

This menu item enables the setting of the requested national lan-

guage.

The following languages are available:

German

English

French

Spanish

Russian

Italian

Dutch

Portuguese

Polish

Czech

Turkish

Setup - Current output 1

and 2 (min./max.)

Lock/release setup - Ad-

justment

Display - Language