9 Diagnostics and service

VEGAFLEX 86 • 4 … 20 mA/HART - four-wire

41845-EN-130314

7. Cable with gravity weight: Fasten cable with the pins, torque 7 Nm

(5.16 lbf ft)
Cable with centering weight: Fasten cable with the pins, torque

7 Nm (5.16 lbf ft) and fix the clamping part on the centering

weight.

8. Enter new probe length and then carry out a fresh adjustment

(see "Setup procedure, Carrying out min. adjustment - Carrying

out max. adjustment").

4

1

1

2

2

3

A

B

C

45 mm (1.77")

100 mm

(3.94")

25 mm (0.98")

50 mm

(1.97")

Fig. 37: Shortening the cable probe
A Gravity weight - cable ø 4 mm

B Gravity weight - cable ø 2 mm

C Centering weight - cable ø 2 mm

1 Pins

2 Thread M8 for eye-bolt

3 Fixing screw - centering weight

9.7 Software update

The following components are required to update the sensor soft-

ware:

Sensor

Voltage supply

Interface adapter VEGACONNECT 4

PC with PACTware

Current sensor software as file

You can find the actual sensor software as well as detailed infor-

mation of the procedure under "www.vega.com/downloads" and

"Software".
You can find information about the installation in the download file.
Caution:

Instruments with approvals can be bound to certain software ver-

sions. Therefore make sure that the approval remains effective with a

software update.
You can find detailed information on www.vega.com/downloads and

"Approvals".