VEGA VEGAFLEX 81 Modbus and Levelmaster protocol User Manual

Page 21

Advertising
background image

21

4 Mounting

VEGAFLEX 81 • Modbus and Levelmaster protocol

41828-EN-130314

Keep in mind that buildup can form on the spacers. Strong buildup

can influence the measurement.

1

2

3

Fig. 13: Position of the spacer or centering weight
1 Rod probe with spacer (PEEK)

2 Cable probe with centering weight

3 Spacer (PEEK) on the gravity weight of a cable probe

Note:

Measurement in a standpipe is not recommended for extremely

adhesive products.
Instructions for the measurement:

The 100 % point should not be above the upper tube connection

to the vessel

The 0 % point should not be below the lower tube connection to

the vessel

A false signal suppression with integrated sensor is generally

recommended to reach the maximum possible accuracy

If there is a danger of the cable probe touching the vessel wall during

operation due to product movements or agitators etc., the measuring

probe should be securely fixed.
In the gravity weight there is an internal thread (M8), e.g. for an eye-

bolt (optional) - (article no. 2.1512).
Make sure that the probe cable is not completely taut. Avoid tensile

loads on the cable.
Avoid undefined vessel connections, i.e. the connection must be

either grounded reliably or isolated reliably. Any undefined change of

this requirement can lead to measurement errors.

In case of difficult installation conditions, the probe can be also

mounted laterally. For this purpose, adapt the rod with rod extensions

or bow-shaped segments.

Fixing

Rod extensions

Advertising