VEGA VEGAFLEX 81 Modbus and Levelmaster protocol User Manual

Page 76

Advertising
background image

76

11 Supplement

VEGAFLEX 81 • Modbus and Levelmaster protocol

41828-EN-130314

L

0

-15 mm

(-0.591")

2 mm

(0.079")

-2 mm

(-0.079")

15 mm

(0.591")

0,3 m

(11.811")

0,15 m

(5.906")

0,08 m

(3.15")

0,05 m

(1.969")

1

1

Fig. 41: Deviation VEGAFLEX 81 in cable version ø 2 mm (0.079 in), in oil
1 Dead band - no measurement possible in this area

L Probe length

0

-15 mm

(-0.591")

2 mm

(0.079")

-2 mm

(-0.079")

15 mm

(0.591")

0,3 m

(11.811")

0,15 m

(5.906")

0,15 m

(5.906")

20 mm

(0.787")

0,05 m

(1.969")

1

1

L

Fig. 42: Deviation VEGAFLEX 81 in cable version ø 4 mm (0.157 in), in oil
1 Dead band - no measurement possible in this area

L Probe length

Repeatability

≤ ±1 mm

Variables influencing measurement accuracy
Temperature drift - Digital output

±3 mm/10 K relating to the max. measuring range or

max. 10 mm (0.394 in)

Additional deviation through electromag-

netic interference acc. to EN 61326

< ±10 mm (< ±0.394 in)

Advertising