31

6 Set up with the display and adjustment module

VEGAFLEX 81 • Modbus and Levelmaster protocol

41828-EN-130314

Linearization

A linearization is necessary for all vessels in which the vessel volume

does not increase linearly with the level - e.g. a horizontal cylindri-

cal or spherical tank, when the indication or output of the volume is

required. Corresponding linearization curves are preprogrammed

for these vessels. They represent the correlation between the level

percentage and vessel volume.
The linearization applies for the measured value indication and the

current output. By activating the suitable curve, the percentage vessel

volume is displayed correctly.
False signal suppression

High sockets and internal vessel installations cause interfering reflec-

tions and can influence the measurement.
A false signal suppression detects, marks and saves these false

signals so that they are no longer taken into account for the level and

interface measurement. We generally recommend carrying out a false

signal suppression to achieve the best possible accuracy. This should

be done with the lowest possible level so that all potential interfering

reflections can be detected.
Enter the actual distance from the sensor to the product surface.
All interfering signals in this section are detected by the sensor and

stored.
The instrument carries out an automatic false signal suppression

as soon as the probe is uncovered. The false signal suppression is

always updated.

6.5 Parameter adjustment - Extended adjustment

For technically demanding measurement loops you can carry out

extended settings in "Extended adjustment".

The main menu is divided into five sections with the following func-

tions:

Setup: Settings, e.g. measurement loop name, medium, vessel,

adjustment, signal output, device unit, false signal suppression,

linearization curve
Display: Settings, e.g., for language, measured value display, lighting
Diagnosis: Information, e.g. on instrument status, pointer, measure-

ment reliability, simulation, echo curve
Additional adjustments: Reset, date/time, reset, copy function

Linearization