4 Mounting

VEGABAR 86 • Modbus and Levelmaster protocol

46296-EN-131107

2

1

Fig. 4: Temperature ranges
1 Process temperature

2 Ambient temperature

4.2 Ventilation and pressure compensation

Ventilation and pressure compensation are carried out with VE-

GABAR 86 via a filter element. It is air permeable and moisture-

blocking.
Caution:

The filter element causes a time-delayed pressure compensation.

When quickly opening/closing the housing cover, the measured value

can change for approx. 5 s by up to 15 mbar.
For effective ventilation, the filter element must always be free of

buildup.
Caution:

Do not use a high-pressure cleaner. The filter element could be dam-

aged, which would allow moisture into the housing.
The following paragraphs describe how the filter element is arranged

in the different instrument versions.

The filter element is integrated in the process assembly. It is located in

a rotatable metal ring and has the following function:

Atmospheric pressure compensation (with relative pressure meas-

uring ranges)

Turn the metal ring in such a way that the filter element points down-

ward after installtion of the instrument. This provides better protection

against buildup.

Filter elements

Instruments in Ex-d ver-

sion