10 Supplement

VEGABAR 86 • Modbus and Levelmaster protocol

46296-EN-131107

Nominal range

Overload capacity, max.

pressure

Overload capacity, min. pres-

sure

0 … 25 bar/0 … 2500 kPa

130 bar/13000 kPa

0 bar abs.

Nominal measuring ranges and overload capacity in psi
The specifications are only an overview and refer to the measuring cell. Limitations due to the

material and version of the process fitting as well as the selected pressure type are possible. The

specifications on the nameplate apply.

Nominal range

Overload capacity, max.

pressure

Overload capacity, min. pres-

sure

Gauge pressure
0 … +0.4 psig

+75 psig

-0.725 psig

0 … +1.5 psig

+225 psig

-2.901 psig

0 … +5 psig

+435 psig

-11.60 psig

0 … +15 psig

+510 psig

-14.51 psig

0 … +30 psig

+725 psig

-14.51 psig

0 … +150 psig

+1300 psig

-14.51 psig

0 … +300 psig

+1900 psig

-14.51 psig

Absolute pressure
0 … 1.5 psi

225 psig

0 psi

0 … 5 psi

435 psi

0 psi

0 … 15 psi

510 psi

0 psi

0 … 30 psi

725 psi

0 psi

0 … 150 psi

1300 psi

0 psi

0 … 300 psi

1900 psi

0 psi

Output variable
Output

Ʋ Physical layer

Digital output signal according to standard EIA-485

Ʋ Bus specifications

Modbus Application Protocol V1.1b, Modbus over serial

line V1.02

Ʋ Data protocols

Modbus RTU, Modbus ASCII, Levelmaster

Max. transmission rate

19.2 Kbit/s

Dynamic behaviour output
Run-up time approx.

10 s

Dynamic characteristics, depending on medium, temperature and, if applicable, chemical seal