VEGA VEGABAR 87 HART and accumulator pack - Operating Instructions User Manual

Page 26

Advertising
background image

26

6 Set up with the display and adjustment module

VEGABAR 87 • HART and accumulator pack

45045-EN-131107

2

1

100%

0%

2

m

(78.74

")

Fig. 14: Parameter adjustment example "Min./max. adjustment, level measure-

ment"
1 Min. level = 0 % corresponds to 0.0 mbar

2 Max. level = 100 % corresponds to 196.2 mbar

If these values are not known, an adjustment with levels of for exam-

ple 10 % and 90 % is also possible. By means of these settings, the

real filling height is then calculated.
The real product level during the adjustment is not important, because

the min./max. adjustment is always carried out without changing the

product level. These settings can be made ahead of time without the

instrument having to be installed.
Note:

If the adjustment ranges are exceeded, the entered value will not be

accepted. Editing can be interrupted with [ESC] or corrected to a

value within the adjustment ranges.

Proceed as follows:
1. Select the menu item "Setup" with [->] and confirm with [OK].

Now select with [->] the menu item "Adjustment", then "Min.

adjustment" and confirm with [OK].

2. Edit the percentage value with [OK] and set the cursor to the

requested position with [->].

3. Set the requested percentage value (e.g. 10 %) with [+] and save

with [OK]. The cursor jumps now to the pressure value.

4. Enter the pressure value corresponding to the min. level (e.g.

0 mbar).

Setup - Min. adjustment