10 Supplement

VEGABAR 87 • HART and accumulator pack

45045-EN-131107

Nominal range

Overload capacity, max.

pressure

Overload capacity, min. pres-

sure

0 … +5 psig

+435 psig

-11.60 psig

0 … +15 psig

+510 psig

-14.51 psig

0 … +30 psig

+725 psig

-14.51 psig

0 … +150 psig

+1300 psig

-14.51 psig

0 … +300 psig

+1900 psig

-14.51 psig

Absolute pressure
0 … 15 psi

510 psi

0 psi

0 … 30 psi

725 psi

0 psi

0 … 150 psi

1300 psi

0 psi

0 … 300 psi

1900 psi

0 psi

Reference conditions and actuating variables (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1

Ʋ Temperature

+15 … +25 °C (+59 … +77 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Determination of characteristics

Limit point adjustment according to IEC 61298-2

Characterstic curve

Linear

Reference installation position

upright, diaphragm points downward

Influence of the installation position

< 0.2 mbar/20 Pa (0.003 psig)

Deviation (according to IEC 60770)
Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to the

analogue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal

measuring range/set span.
The specified values correspond to the value F

Kl

in chapter "Calculation of the total deviation".

Accuracy class

Non-linearity, hysteresis and re-

peatability with TD 1 : 1 up to 5 : 1

Non-linearity, hysteresis and re-

peatability with 5 : 1

0.1 %

< 0.1 %

< 0.02 % x TD

Influence of the product or ambient temperature
Thermal change zero signal and output span
Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to the

analogue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal

measuring range/set span.
The thermal change of zero signal and output span corresponds to the value F

T

in chapter "Calcu-

lation of the total deviation (according to DIN 16086)".
Ceramic/Metal measuring cell - Standard

Medium or ambient temperature T
-40 … 0 °C (-40 … +32 °F)

< {0.15 % + 0.015 %/K x (-T)} x {0.5+0.5 x TD}