2 principle of operation – VEGA VEGAPULS 61 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA__HART two-wire User Manual

Page 10

Advertising
background image

T

he type label contains the most important data for identification and

use of the instrument:

l

I

nstrument type

l

A

rticle and serial number device

l

A

rticle numbers, documentation

l

T

echnical data: Approvals, antenna type, process fitting, process

seal/temperature, signal output, voltage supply, protection, pro-
tection class

l

SIL

identification (with SIL rating ex works)

W

ith the serial number, you can access the delivery data of the

instrument via www.vega.com, "VEGA Tools" and "serial number
search
". In addition to the type label outside, you can also find the
serial number on the inside of the instrument.

3

.2 Principle of operation

VEGAPULS

61

is a radar sensor in K-band (emitting frequency

approx. 26 GHz) for continuous level measurement.

T

he version with encapsulated antenna system is particularly

suitable for level measurement of aggressive liquids in small vessels.

T

he version with plastic horn antenna is particularly suitable for flow

measurement in open flumes or gauge measurement in bodies of
water.

T

he electronics with increased sensitivity enables the use of

VEGAPULS

61

also in applications with very poor reflective properties

or products with low ε

r

value.

T

he antenna of the radar sensor emits short radar pulses with a

duration of approx. 1 ns. These pulses are reflected by the product
and received by the antenna as echoes. The running time of the radar
pulses from emission to reception is proportional to the distance and
hence to the level. The determined level is converted into an
appropriate output signal and outputted as measured value.

T

wo-wire electronics 4 … 20 mA/HART for power supply and

measured value transmission over the same cable.

T

he supply voltage range can differ depending on the instrument

version.

T

he data for power supply are specified in chapter "Technical data".

T

he backlight of the indicating and adjustment module is powered by

the sensor. The prerequisite for this is a supply voltage at a certain
level. The exact voltage specifications are stated in chapter "Technical
data
".

Type label

Application area

Functional principle

Voltage supply

10

VEGAPULS

61 • 4 … 20

mA/HART two-wire

3 P

roduct description

28434

-EN

-100426