4 switch on phase – VEGA VEGAPULS 61 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA__HART four-wire User Manual

Page 28

Advertising
background image

Information:
K

eep in mind that the indicating and adjustment module must only be

used in the electronics compartment.

4 ... 20 mA

PE

/ L
/ N

L1 N

GND

1

2

1

2

3

4

4...20mA

IS

Fig. 23: Wiring plan, double chamber housing

1

Voltage supply

2

Signal output

5

.4 Switch on phase

A

fter connecting VEGAPULS 61 to power supply or after a voltage

recurrence, the instrument carries out a self-check for approx. 30
seconds:

l

I

nternal check of the electronics

l

I

ndication of the instrument type, the firmware as well as the

sensor TAGs (sensor designation)

l

O

utput signal jumps briefly (approx. 10 seconds) to the set fault

current

T

hen the corresponding current is outputted to the cable (the value

corresponds to the actual level as well as the settings already carried
out, e.g. factory setting).

Wiring plan

Switch on phase

28

VEGAPULS

61 • 4 … 20

mA/HART four-wire

5 C

onnecting to power supply

28439

-EN