7-2. If you enable the function of item B, once the UPS transfer to battery mode for XX minutes (XX<AA) and
the UPS start to inform the low battery warning. Then the WinPower would send the command to shutdown the
PC. After CC minutes, the UPS would also shutdown automatically. It means the UPS will transfer to battery
mode for XX+CC minutes.

7-3. If you disable the function of item B, once the UPS transfer to battery mode for XX minutes (XX<AA) and
the UPS start to inform the low battery warning. The UPS would still keep working till AA minutes. If the UPS
could not support the load till AA minutes, the UPS and the load (PC) would shutdown directly when the battery
is empty. If the UPS could support the load till AA minutes, when the backup time reaches the value of AA
minutes, the WinPower would send the command to shutdown the PC. After the CC minutes, the UPS would
also shutdown automatically. It means the UPS will transfer to battery mode for AA+CC minutes.


8. There are also two main functions on the operation of the “Shutdown Remote Agent” as below.

The item of “Shutdown” means that when the UPS of the Agent is going to shutdown, the WinPower
will send out the shutdown command to the remote PC of the IP that you added in the below space.

The item of “On Battery” means that when the UPS of the Agent transfer to battery for XX minutes, the
WinPower will send out the shutdown command to the remote PC of the IP that you added in the below
space.
Hence, you only can change the time setting when you select this item.

If there are more than one UPS in the shutdown conditions list, you can set different shutdown
condition of each UPS according your actual status.
For example, if there are two UPS (UPS A and UPS B) in the shutdown conditions list, UPS A and UPS
B supply power to the remote agent at the same time. Once there is no power for the remote agent, the
remote agent will be shut down safely. You should set shutdown condition of UPS A and UPS B, the
remote agent won’t be shut down until all the condition of UPS A and UPS B is met.

9. Below setting is on the Agent.