Np r i, Rate - ir, 3 motor nominal current – R&M Materials Handling VARIABLE SPEED CONTROLS CMXC 022 Service Manual User Manual

Page 14

Advertising
background image

R&M Materials Handling, Inc.

4501 Gateway Boulevard

Springfield, Ohio 45502

P.: (937) 328-5100

FAX: (937) 325-5319

14/14

R&M Materials Handling, Inc. reserves the right to alter or amend the above information without notice.

n

p

R

I

S

NOM

*

*

rate

-

IR

=

I

NOM

Nominal current of the motor (one motor)

R

s

Stator resistance, measured between inverter
terminals X2:4-5

P

Number of polepairs

N

Number of motors connected to inverter

Settings:

IR-rate

Setting of S4

90 -

S4-3 = 0 ; S4-4 = 0

60 - 89

S4-3 = 1 ; S4-4 = 0

40 - 59

S4-3 = 0 ; S4-4 = 1

- 37

S4-3 = 1 ; S4-4 = 1

m

For conical brake motors it is recommended to set the IR-compensation one step higher than the IR-rate indicates.
The reliable operation of the brake must be verified during start-up.

3.6.3 Motor nominal current

Motor nominal current is set by switches S5-1 and S5-2 as follows:

Check the nominal current of the motor from the rating plate

Calculate the total current by multiplying the current by the number of the motors

Select the settings according to the table below

I

NOM,TOTAL

S5-1

S5-2

0…1.8A

0

0

1.9A…2.7A

1

0

2.8A…3.5A

0

1

>3.5A

1

1


For example: there are two 1.5A motors

Setting is S5-1=0 and S5-2=1.