Fault code

Possible cause

Checking

F 7
Saturation trip

Very high overload or defective
component

Reset: switch power off and restart after the lamps
of keypad are off.
Check:
− motor and motor cable insulation

− measure main circuit diodes and IGBT

transistors

If the fault comes again, change the D2V.

F8
System fault

System fault due to component failure
or faulty operation.

Reset: switch power off and restart after the lamps
of keypad are off.
Check:
− read fault extension code and contact

authorized service

If the fault comes again, change the D2V.

F 9
Undervoltage

DC-bus voltage has dropped below
333Vdc
− mains supply voltage interrupted

− inverter fault can also cause an

undervoltage trip

− external fault during run may cause

an undervoltage trip

In case of temporary supply voltage break, reset
the fault and start again. Check mains input.
− if mains supply is correct, an internal failure

has occurred

− contact authorized service

F 10
Input line supervision

One input line phase is missing or
supply voltage parameter is wrong

Check:
− supply voltage

− mains connection

F 11
Output phase
supervision

Current supervision has sensed that
one of the motor phases has no current

Check:
− motor cable connections

− measure motor phase currents and compare to

display value

F 12
Braking chopper
supervision

Braking chopper or braking resistor
circuit has failed. Fault appears if
− braking resistor is broken

− braking chopper is broken

− braking resistor is not installed

Reset: switch power off and restart after the lamps
of keypad are off.
Check:
− braking resistor and cable resistance and

insulation resistance

− measure braking transistor IGBT and free

wheeling diodes

− if resistor is OK, then the chopper is broken

− contact authorized service

F 13
Inverter
undertemperature

Temperature of heat sink is below
acceptable operating level (-10°C
/14°F)

Check
− ambient temperature

− cubicle heating

− inverter cooling fan activation (continuous /

temperature limit)

F 14
Inverter
overtemperature

Temperature of heat sink is over
acceptable operating level
+90°C (194°F).
Overtemperature warning is issued
when the heat sink temperature
exceeds +85°C (185°F)

Check:
− ambient temperature

− inverter cooling fan operation

− cooling air flow through heat sink

− heat sink is not dusty

F16
Motor
overtemperature

Mathematical motor temperature model
has detected motor overheating. Motor
is overloaded.

Check:
− motor load

− if no overload exists, then check motor

temperature model parameters

F 22
F 23
EEPROM checksum
fault

Parameter save error
− interference fault

− component failure (control unit)

After power off the inverter will automatically load
factory default parameter settings. D2H/D2C does
not work properly nor enable driving after this
fault.
Check:
− all parameter settings

− +24V voltage output loading
If the fault comes again, contact authorized
service.