Data Sheet

CP2000DC54-PE series dc-dc converter

Input: -40Vdc to -72Vdc; Outputs: ±54Vdc @ 2000W; 5Vdc @ 4W

August 20, 2013

©2013 General Electric Company. All rights reserved.

Page 14

Signal Definitions

All hardware alarm signals (Fault, Power_OK, I_Limit, OTW) are open drain FETs. These signals should be pulled HI to either 3.3V or 5V. Maximum sink
current 5mA. An active LO signal (< 0.4Vdc) state is referenced to Logic GRD unless otherwise stated. Contact your Lineage Power representative for
more details.

Function

Label

Type

Description

Output Enable

Enable

Input

If shorted to LOGIC_GRD, the PEM output is enabled when using I

2

C mode of

operation. May also be toggled to reset a latched OFF PEM.

Output Good

Power_OK

Output

An open drain FET; normally HI, indicating output power is present. Changes to LO
when the main output is OFF,

Current Limit

I_Limit

Output

An open drain FET; normally HI, indicating normal operation. Changes to LO when
in current limit,

I

2

C Interrupt

Alert#_0
Alert#_1

Output

Interrupt signal via I

2

C lines indicating that service is requested from the host

controller. This signal pin is pulled up to 3.3V via a 10kΩ resistor and switches to
active LO when an interrupt occurs.

PEM Fault

Fault

Output

Indicates that an internal fault exists. An open drain FET; normally HI, changes to
LO.

Module Present

MOD_PRES

Output

Used to Indicate presence of PEM.

ON/OFF

ON/OFF

Input

Short pin, connects last and breaks first; used to activate and deactivate output
during hot-insertion and extraction, respectively. Ref: V_OUT (-DC)

Margining

Margin

Input

Allows changing of output voltage through an analog voltage input or via resistor
divider.

Over-Temperature Warning

OTW

Output

An open drain FET; normally HI, changes to LO approximately 5°C prior to thermal
shutdown.

PEM address

Unit_addr

Input

Voltage level addressing of PEMs within a single shelf. Ref: V_OUT (-DC).

Shelf Address

Shelf_addr

Input

Voltage level addressing of PEMs within multiple shelves. Ref: V_OUT (-DC).

Back bias

8V_INT

_

Diode OR’ed 8Vdc drain; used to back bias microprocessors and DSP of failed PEM
from operating PEMs. Ref: V_OUT (-DC).

Mux Reset

Reset

Input

Resets the I

2

C lines to I

2

C line 0.

Standby power

5VA

Output

5V at 0.75A provided for external use by either adjacent power supplies or the
using system.

Current Share

Ishare

-

A single wire interface between each of the power unit forces them to share the
load current. Ref: V_OUT (-DC).

I

2

C Line 0

SCL_0, SDA_0

Input

I

2

C line 0.

I

2

C Line 1

SCL_1, SDA_1

Input

I

2

C line 1.

Advertising