Data sheet, Pmbus, Commands – GE Industrial Solutions CP2000DC54-PE User Manual

Page 8: Command descriptions

Advertising
background image

GE

Data Sheet

CP2000DC54-PE series dc-dc converter

Input: -40Vdc to -72Vdc; Outputs: ±54Vdc @ 2000W; 5Vdc @ 4W

August 20, 2013

©2013 General Electric Company. All rights reserved.

Page 8

ensure that only the final state of the power supply is
captured.

Successive read backs:

Successive read backs to the power

supply should not be attempted at intervals faster than
every one second. This time interval is sufficient for the
internal processors to update their data base so that

successive reads provide fresh data.

Device ID:

Address bits A2, A1, A0 set the specific address of

the power supply. The least significant bit x (LSB) of the

address byte configures write [0] or read [1] events. In a

write command the system instructs the power supply. In a
read command information is being accessed from the
power supply.

Address Bit

7 6 5 4 3 2 1 0

PCA9541

1 1 1 0 A2 A1 A0 R/W

Micro

controller

1 0 0 0 A2 A1 A0 R/W

External

EEPROM

1 0 1 0 A2 A1 A0 R/W

Global

Broadcast 0 0 0 0 0 0 0 0

MSB

LSB


The Global Broadcast instruction executes a simultaneous
write instruction to all power supplies. A read instruction
cannot be accessed globally. The three programmable
address bits are the same for all I

2

C accessible devices

within the power supply.

PMBus

TM

Commands

Standard instruction:

Up to two bytes of data may follow

an instruction depending on the required data content.
Analog data is always transmitted as LSB followed by MSB.
PEC is mandatory and includes the address and data fields.

1 8 1

8 1

S Slave

address Wr A Command

Code A

8 1 8 1

8

1

1

Low data byte

A High

data

byte A PEC A P

Master to Slave Slave to Master
SMBUS annotations; S – Start , Wr – Write, Sr – re-Start, Rd –
Read,
A – Acknowledge, NA – not-acknowledged, P – Stop

Direct mode data format:

The Direct Mode data format is

supported, where y = [ mX + b ] x 10

R

. In the equation, y is

the data value from the controller and x is the ‘real’ value
either being set or returned.

For example, to set the output voltage to 50.45V

DC

, Multiply

the desired set point by the m constant, 50.45 x 400 =
20,180. Convert this binary number to its hex equivalent:
20,180b = 0x4ED4. The result is sent LSB=0xD4 first, then
MSB=0x4E.
The constants are

FUNCTION

Operation

m

b

R

Output voltage
Output voltage shutdown

Write / read

400

0

0

Output Current

read

5

0

0

Temperature

read

1

0

0

Input Voltage

read

1

75

0

Input Power

read

1

0

0

Fan Speed setting ( % )

read

1

0

0

Fan speed in RPM

read

100

0

0

PMBus

TM

Command set:

Command

Hex

Code

Data
Field

Function

Operation 01

1

Output

ON/OFF

Clear_Faults 03

0

Clear

Status

Vout_command 21

2

Set

Vout

Vout_OV_fault_limit

40

2

Set OV fault limit

Read_status

D0

10

Read Status, V

out

, I

out

, T

LEDs test ON

D2

0

Test LEDs

LEDs test OFF

D3

0

Service_LED_ON D4

0

Service

LED

Service_LED_OFF D5 0

Enable_write

D6

0

Enable EEPROM write

Disable_write D7

0

Disable

EEPROM

write

Inhibit_restart D8

0

Latch

upon

failure

Auto_restart D9

0

Hiccup

Isolation_test DA

0

Perform

isolation

test

Read_input_string

DC

2

Read Vin and Pin

Read_firmware_rev DD 3 Firmware

revisions

Read_run_timer DE

3

Accumulated

ON

state

Fan_speed_set

DF

3

Fan speed control

Fan_normal_speed E0 0

Stop

fan

control

Read_fan_speed

E1

4

Fan control & speed

Stretch_LO_25ms

E2

0

Production test feature

Command Descriptions

Operation (01h) :

By default the Power supply is turned ON

at power up as long as ENABLE is active LO. The Operation
command is used to turn the Power Supply ON or OFF via
the PMBus. The data byte below follows the OPERATION
command.

FUNCTION

DATA BYTE

Unit ON

0x80

Unit OFF

0x00


To RESET the power supply cycle the power supply OFF, wait
at least 2 seconds, and then turn back ON. All alarms and
shutdowns are cleared during a restart.

Clear_faults (03h):

This command clears information bits in

the STATUS registers, these include:

Isolation OK

Isolation test failed

Restarted OK

Invalid command

Invalid data

PEC error

Vout_Command (21h) :

This command is used to change

the output voltage of the power supply. Changing the output
voltage should be performed simultaneously to all power

supplies operating in parallel using the Global Address
(Broadcast) feature. If only a single power supply is
instructed to change its output, it may attempt to source all

the required power which can cause either a power limit or
shutdown condition.